Hydrant flow test (Pitot), projected to 1.4 bar

Enter static pressure, residual pressure during flow and Pitot pressure at the outlet. Get test flow and the supply available at 1.4 bar residual.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

The hydrant flowed 2,023 L/min (33.7 L/s) with 3.00 bar residual. Projected to 1.4 bar residual, the supply delivers about 49.9 L/s.

Inputs

bar
bar
Measured at the test hydrant while the flow hydrant is open
bar
mm
2½" = 63.5 mm; 4" = 101.6 mm
bar

Enter your data, then press Calculate (or Enter).

Preliminary results

Test flow33.7L/s
L/min2,023L/min
Available at residual 1.4 bar49.9L/s
StepResultBasis
Test flowQ = 0,6664 × 0.9 × 63.5² × √0.702,023 L/minNFPA 291
Pressure-drop ratio(Ps − Pr)/(Ps − Pf) = (4.50 − 1.4)/(4.50 − 3.00)2.067NFPA 291
Available flowQR = QF × ratio^0,542,994 L/min = 49.9 L/sNFPA 291 ⚠
Sources and assumptions. NFPA 291: Q = 0.6664·C·d²·√Pp (L/min; d mm; Pp bar), QR = QF·((Ps − Pr)/(Ps − Pf))^0.54. 1.4 bar (20 psi) residual is the usual reference for fire water supply ⚠. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Frequently asked questions

Why project to 1.4 bar residual?

1.4 bar (20 psi) is the minimum residual commonly used to rate a water main: the flow at this point shows what the hydrant and main can supply to fire engines.

How is the Pitot reading taken?

Hold the Pitot blade in the centre of the stream about half a diameter from the outlet; read static and residual on a cap gauge at the test hydrant.