Choose the pipe size and straight run length. Get maximum spacing, number of hangers, rod size and load per hanger.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

A 30 m run of DN100 pipe needs hangers at most 4.6 m apart: 7 hangers, M10 (3/8") rod, design load about 595 kg each.

Inputs

m

Enter your data, then press Calculate (or Enter).

Preliminary results

Max spacing4.6m
Hangers7pcs
RodM10(3/8")
Design load per hanger595kg
StepResultBasis
Pipe + water12.18 + 8.7120.89 kg/m—
Number of hangers⌈30/4.6⌉7 pcsNFPA 13 ⚠
Design load5 × 20.89 × 4.6 + 114595 kgNFPA 13 ⚠
Sources and assumptions. NFPA 13: steel pipe hanger spacing (DN25–DN32: 3.7 m; DN40 and up: 4.6 m), rod size by pipe size, hangers rated for 5 × water-filled pipe weight plus 114 kg ⚠. Every branch needs at least one hanger; add at ends and changes of direction. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Suggested materials

Pipe hanger DN100 (clamp + M10 (3/8") rod)7 pcs
Threaded rod M10 (3/8")per drawing

Steel pipe hanger spacing

SizeMax spacingRodPipe + water (kg/m)
DN25 (1")3.7 mM10 (3/8")2.99
DN32 (1-1/4")3.7 mM10 (3/8")4.11
DN40 (1-1/2")4.6 mM10 (3/8")4.94
DN50 (2")4.6 mM10 (3/8")7.25
DN65 (2-1/2")4.6 mM10 (3/8")10.16
DN80 (3")4.6 mM10 (3/8")13.51
DN100 (4")4.6 mM10 (3/8")20.89
DN125 (5")4.6 mM12 (1/2")29.82
DN150 (6")4.6 mM12 (1/2")38.63

Frequently asked questions

How far apart are sprinkler pipe hangers?

Steel DN25–DN32 at most 3.7 m, DN40 to DN200 at most 4.6 m (NFPA 13). Short branches still need at least one hanger.

What rod size?

Pipe up to DN100: M10 (3/8") rod; DN125–DN200: M12 (1/2").