Enter the flow and duration of each system (from the Sprinkler, Hydrant and Outdoor tools) and the building height. The tool returns the minimum tank volume and main and jockey pump data.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

Minimum fire water tank 144.0 m³. Main pump 144 m³/h at 45 m (4.4 bar), 37.0 kW motor; jockey pump about 1.4 m³/h at 52 m.

Inputs

Fire water

L/s
From the Sprinkler tool (q × F)
min
L/s
From the Indoor hydrant tool
min
L/s
Leave 0 if outdoor hydrants draw from the public main
min
L/s
Continuous supply into the tank; 0 if unsure

Pump head

m
From the lowest tank water level
bar
Most remote sprinkler or top-floor nozzle
m
From the Pressure loss tool; 10–20 m preliminary
η

Enter your data, then press Calculate (or Enter).

Preliminary results

Min. tank144.0m³
Pump flow144m³/h
Head45m
Motor37.0kW
StepResultBasis
Sprinkler water3,6 × 30.0 × 60/60108.0 m³TCVN 7336:2021 ⚠
Indoor hydrant water3,6 × 10.0 × 60/6036.0 m³TCVN 3890:2023 ⚠
Tank volumeΣW144.0 m³—
Main pump flow30.0 + 10.0 L/s144 m³/h—
Head H = Z + P·10.2 + ΔH20 + 1.0 × 10,2 + 1545.2 m—
Shaft power9,81 × 0.040 × 45.2 / 0.6527.3 kW—
Motor (15 % margin)≥ 1,15 × 27.337.0 kW—
Jockey pump~1 % Q; H + 7 m1.4 m³/h · 52 mNFPA 20 ⚠
  • Main and standby pumps have the same duty; standby is diesel or on a second power source.
  • The jockey pump keeps system pressure and starts the main pump when pressure drops.
  • Each pump has its own suction; the fire reserve is not used for domestic water.
Sources and assumptions. W = Σ 3.6·Q·t (Q L/s, t h); sprinkler duration per TCVN 7336:2021, hydrants 1 h, outdoor 3 h ⚠. H = Z + P·10.2 + ΔH; P_shaft = ρ·g·Q·H/η, motor ≥ 1.15·P_shaft. Jockey ~1 % of main flow, about 0.7 bar higher head (NFPA 20) ⚠. Final pump selection follows the maker's curve. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Suggested materials

Main fire pump (electric) 144 m³/h – 45 m, 37.0 kW1
Standby fire pump (diesel or electric) 144 m³/h – 45 m1
Jockey pump 1.4 m³/h – 52 m1
Fire pump controller1

Frequently asked questions

How big should a factory fire water tank be?

Sum of simultaneous flows × duration: e.g. sprinklers 30 L/s × 1 h = 108 m³ plus hydrants 10 L/s × 1 h = 36 m³ gives 144 m³, before outdoor water if taken from the tank.

Why a jockey pump?

Fire mains always leak slightly; the jockey keeps pressure so the main pump does not cycle, and when a sprinkler opens the pressure drop starts the main pump.