Outdoor fire water flow for factory buildings

Enter the fire resistance degree, fire hazard class and building size. The tool computes the building volume, looks up the outdoor fire water flow for one fire, the 3-hour water storage and the main supply pipe size.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

Factory of degree II, class C, 60 × 30 × 9.0 m (volume 16,200 m³): outdoor fire water flow 15 L/s, storage 162 m³ for 3 hours.

Inputs

Degree I–V as stated in the fire safety design, based on the fire resistance of columns, beams, walls and roof (QCVN 06:2022/BXD). Ask the designer if unsure. What is fire resistance degree?
Depends on materials produced or stored. A, B: explosive gases, vapours, dusts; C: combustible materials (wood, paper, textiles, plastics); D: non-combustible materials processed hot (forging, casting, welding); E: non-combustible materials cold (cold machining). What is hazard class?
m
m
m
Outer dimensions of the building in metres. Height from floor to ridge. For several fire compartments, use the largest one.

Enter your data, then press Calculate (or Enter).

Preliminary results

Area1,800m²
Volume16,200m³
Flow15L/s
Water 3 h162m³
StepResultBasis
Building areaS = 60 × 301,800 m²—
Building volumeV = S × 9.016,200 m³QCVN 06:2022/BXD
Volume column in the table16.2 thousand m³5–20 thousand m³TCVN 2622:1995 ⚠
Outdoor fire water flow (one fire)Degree II · C ⚠15 L/sQCVN 06:2022 · TCVN 2622 ⚠
Water storageW = 3,6·Q·3162 m³QCVN 06:2022/BXD ⚠
Preliminary main pipev ≤ 2,5 m/s ⚠DN100BS 1387
Sources and assumptions. Outdoor fire water flow for production buildings by fire resistance, hazard class and volume: QCVN 06:2022/BXD, carried over from TCVN 2622:1995 (⚠ values to be checked against the original). Fire duration 3 h: W = 3.6·Q·3. Not covered: high-bay warehouses, light roofs wider than 60 m, industrial parks with simultaneous fires. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Suggested materials

Outdoor fire hydrant D100 (2 × D65 outlets)Along internal roads, spacing per QCVN 06 ⚠per drawing
Fire water tank ≥ 162 m³Add sprinkler and indoor hose water if the tank is shared1 set
Galvanized steel pipe DN100 (outdoor ring main)Preliminary v ≤ 2.5 m/s at 900 L/min ⚠per drawing
Outdoor fire pump set 54 m³/hDuty and standby pumps; head per network layout1 set

Glossary

What is the fire resistance degree?

The fire resistance degree rates how well the whole building withstands fire, in 5 degrees: degree I is the best, degree V the weakest.

It is set by the fire resistance (in minutes) of the main elements: columns, beams, load-bearing walls, floors and roof, using criteria R (load-bearing), E (integrity) and I (insulation), e.g. R 120, REI 60.

The weakest element sets the degree of the whole building. See Table 4 of QCVN 06:2022/BXD.

Degree I – II
Reinforced concrete frame, brick walls; or steel frame with approved fire-protective coating or cladding
Degree III
Non-combustible load-bearing structure with lower fire resistance, protected floors and roof
Degree IV – V
Unprotected steel-frame factory with metal roof; timber-structured buildings

Examples for reference only ⚠. The official degree is stated in the approved fire safety design.

What is the fire and explosion hazard class?

The hazard class rates a building (or room) by the substances inside and the production process, from A (most hazardous) to E (least). The higher the class, the stricter the requirements for fire water, separation distances and escape routes.

ClassCharacteristicsExamples
AFlammable gases; flammable liquids (flash point ≤ 28 °C) that can form explosive mixturesLight fuel depots, solvent paint shops, gas stations
BCombustible dusts and fibres; liquids with flash point above 28 °C that can form explosive mixturesFlour mills, cotton spinning, diesel storage
CCombustible solids, hardly flammable liquidsWoodworking, paper, garment, plastics; packaged goods storage
DNon-combustible materials in a hot or molten state, with sparks or flamesForging, casting, hot rolling, welding, boilers
ENon-combustible materials in a cold stateCold machining, steel warehouses, non-combustible storage

Official classification per QCVN 06:2022/BXD and the design ⚠. For buildings with rooms of different classes, the most hazardous room sets the class if it is large enough.

Frequently asked questions

How much outdoor fire water does a class C, degree II factory of 16,000 m³ need?

16,200 m³ falls in the 5–20 thousand m³ column; degree I–II class C needs 15 L/s for one fire. 3-hour storage: 3.6 × 15 × 3 = 162 m³.

Where do I find the fire resistance degree of a factory?

In the approved fire safety design. It depends on the fire resistance of load-bearing structures, walls, floors and roof per QCVN 06:2022/BXD.

What is the difference between hazard classes A, B, C, D, E?

A, B: explosive gases, vapours, dusts or flammable liquids. C: combustible solids and liquids such as wood, paper, textiles, plastics. D: non-combustible materials processed hot. E: non-combustible materials in a cold state.