Acceptance test pressure for fire pipework

Enter the maximum working pressure (usually pump churn plus supply). Get test pressure, holding time and pass criteria.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

Working pressure 10.0 bar: hydrostatic test at 13.8 bar (200 psi) for 2 hours with no leakage.

Inputs

bar
Pump churn pressure plus supply pressure

Enter your data, then press Calculate (or Enter).

Preliminary results

Hydrostatic test13.8bar
Hold2h
Air test—
StepResultBasis
Hydrostatic test pressuremax(13,8; 10.0 + 3,4)13.8 barNFPA 13 ⚠
Pass criteria2 hNo leakage, no pressure lossNFPA 13
Sources and assumptions. NFPA 13 (hydrostatic 200 psi or working + 50 psi, 2 hours; dry air test 40 psi, 24 hours). TCVN 7336:2021 has its own test rules; follow the approved design ⚠. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Frequently asked questions

What pressure is fire pipework tested at?

Per NFPA 13: at least 13.8 bar (200 psi) for 2 hours; above 10.3 bar (150 psi) working pressure, test at working pressure plus 3.4 bar (50 psi).

Where is test pressure measured?

At the lowest point of the section under test; higher points see less, about 0.1 bar per metre of elevation.