Choose commodity group and agent, enter storage height and room height. The tool looks up TCVN 7336:2021 Table 5.2, corrects for ceilings above 10 m, and gives density, design flow, operating heads and 60-minute water supply.

Updated Technical review: KS. Dương Văn TiếnFree, no sign-up
Quick answer

Group 5, water, storage 3.5 m: density 0.320 L/s·m², flow 60.0 L/s, 60-minute water about 216 m³.

Inputs

By the goods and packaging stored ⚠
m
Floor to top of goods; max 5.5 m
m
Floor to ceiling (roof); above 10 m increases density

Enter your data, then press Calculate (or Enter).

Preliminary results

Density0.320L/s·m²
Design flow60.0L/s
60-minute water216m³
Operating heads10heads
StepResultBasis
Storage height bandh = 3.5 m ≤ 5.5 m3–4 mTCVN 7336:2021 Bảng 5.2 ⚠
Table 5.2 (density · minimum flow)Group 5 – ordinary combustibles (paper, wood, textiles, cartons) · Wateri = 0.320 · Q ≥ 60.0 L/sTCVN 7336:2021 Bảng 5.2 ⚠
Ceiling above 10 m (+10 % per 2 m)H = 8.0 m → 1 + 0,1 × 0× 1.0TCVN 7336:2021 Bảng 5.2 chú thích 3
Flow = density × 90 m², not less than table flowmax(0.320 × 90; 60.0)60.0 L/sTCVN 7336:2021 Bảng 5.1 ⚠
Operating heads⌈90 / 9⌉10 headsTCVN 7336:2021 Bảng 5.1 ⚠
Water supply3,6 × 60.0 × 60/60216 m³TCVN 7336:2021 Bảng 5.1
  • Design area 90 m², 9 m² per head, 60-minute discharge (TCVN 7336:2021 Table 5.1 for storage) ⚠.
  • Clearance from top of goods to deflector ≥ 0.5 m (≥ 0.9 m for high-challenge goods).
  • Rack storage above 5.5 m: outside TCVN 7336:2021; needs in-rack sprinklers per tier or ESFR, special design.
  • Which warehouses need automatic suppression: QCVN 10:2025/BCA Table A.1.
Sources and assumptions. Basis: TCVN 7336:2021 Fire protection – Automatic sprinkler systems – Design and installation. Table 5.2: density and minimum flow for storage groups 5, 6, 7 by storage height up to 5.5 m; note 3: rooms higher than 10 m add 10 % per extra 2 m; clause 1.2 and note 5: not applicable to storage above 5.5 m. Table 5.1: design area, duration. Values marked ⚠ come from excerpts, pending check against the original. Results are preliminary, not a hydraulic calculation. ⚠ = code table value to be checked against the original standard. Preliminary results for material selection and budgeting; not a substitute for an approved fire protection design.

Suggested materials

Sprinkler heads (rating per ceiling, K ≥ 115)10 heads operating in the design areaper drawing
Galvanised steel pipe, fittings, hangersper drawing
Fire pump set 216 m³/h (duty, standby, jockey)1 set
Fire water tank ≥ 216 m³1 set

TCVN 7336:2021 Table 5.2: density (L/s·m²) · minimum flow (L/s)

Storage heightGroup 5 · WaterGroup 5 · Foam solutionGroup 6 · WaterGroup 6 · Foam solutionGroup 7 · WaterGroup 7 · Foam solution
≤ 1 m0.08 · 15.00.04 · 7.50.16 · 30.00.08 · 15.0—0.10 · 18.0
1–2 m0.16 · 30.00.08 · 15.00.32 · 60.00.20 · 36.0—0.20 · 36.0
2–3 m0.24 · 45.00.12 · 22.50.40 · 75.00.24 · 45.0—0.30 · 54.0
3–4 m0.32 · 60.00.16 · 30.00.40 · 75.00.32 · 60.0—0.40 · 75.0
4–5.5 m0.40 · 75.00.32 · 37.50.50 · 90.00.40 · 75.0—0.40 · 75.0

Rooms higher than 10 m: multiply density and flow by 1 + 0.1 per 2 m above. Group 7 does not use water. Highlighted cell is the current case. ⚠ pending check against the original.

Frequently asked questions

Can I use this for 8 m high storage?

No. TCVN 7336:2021 covers storage up to 5.5 m only. Higher storage needs in-rack sprinklers or ESFR per NFPA 13, FM Global 8-9, with a dedicated design and approval.

Why is the flow larger than density × 90 m²?

Table 5.2 also gives a minimum flow. Take the larger of density × design area and the table flow.

How about a 14 m ceiling?

Table 5.2 note 3: each 2 m above 10 m adds 10 %. 14 m is 4 m above, two steps, factor 1.2.

Can water protect paint and solvent storage?

Group 7 (flammable liquids) in Table 5.2 lists foam solution only; water cannot extinguish floating liquid fires.

Applicable documents

Documents in force at the update date, applied from 1 July 2026. TCVN standards are mandatory only when a QCVN refers to them; where they differ, the QCVN prevails.

CodeTitleEffective fromStatus
QCVN 10:2025/BCATrang bị, bố trí phương tiện PCCC và CNCH cho nhà và công trình30/12/2025In force
TCVN 7336:2021Hệ thống chữa cháy tự động bằng nước, bọt – Yêu cầu thiết kế, lắp đặtVoluntaryIn force ⚠
QCVN 06:2022/BXD + SĐ1:2023An toàn cháy cho nhà và công trình16/01/2023In force ⚠

See the full list of regulations and standards →