Fire protection provisions and design appraisal check
Enter the building type and size to see which fire protection systems QCVN 10:2025/BCA (in force 30 Dec 2025) requires and whether the fire safety design falls under appraisal per Annex III of Decree 105/2025/ND-CP (replaced by Decree 347/2026/ND-CP, in force 15 Sep 2026).
Hotel, guest house, other accommodation: automatic fire alarm required; automatic suppression not required; fire safety design appraisal to be checked ⚠.
Preliminary results
Systems to provide
| System | Result | Condition | Basis |
|---|---|---|---|
| Automatic fire alarm | Required | ≥ 3 storeys or ≥ 700 m² floor · At this size, standalone detectors may replace the automatic fire alarm system. | QCVN 10:2025/BCA 2.1, QCVN 10:2025/BCA Bảng A.1 · 18 |
| Automatic suppression (sprinkler, gas…) | Not required | ≥ 5,000 m² floor or fire height ≥ 25 m | QCVN 10:2025/BCA 2.5, QCVN 10:2025/BCA Bảng A.1 · 18 |
| Indoor fire hydrants | To be checked ⚠ | Per section 2.4 and Annex B (building type, storeys, volume) ⚠ awaiting the Annex B table. Use the Indoor hydrants tool for a first estimate. | QCVN 10:2025/BCA 2.4, PL B ⚠ |
| Outdoor fire water supply | To be checked ⚠ | Per section 2.3 and Annex C ⚠ awaiting the original table. Exempt when every point of the building is within 400 m horizontally of a hydrant or a public or on-site water source with enough flow (2.3.2). | QCVN 10:2025/BCA 2.3, PL C ⚠ |
| Portable extinguishers | Required | All buildings. Layout per TCVN 7435-1; buildings under construction: at least one ABC powder unit ≥ 4 kg per 500 m² of floor per storey, travel ≤ 25 m (2.6.5). | QCVN 10:2025/BCA 2.6 |
| Emergency lighting, exit signs | Required | By building type and escape routes (section 2.2, TCVN 13456:2022). | QCVN 10:2025/BCA 2.2 |
| Fire safety design appraisal | To be checked ⚠ | Annex III of Decree 347/2026 not yet checked for this building type ⚠. Send us the documents to check. | NĐ 105/2025 PL III, thay bởi NĐ 347/2026 ⚠ |
QCVN 10:2025/BCA Table A.1: automatic alarm and suppression by building type
| No. | Building type | Alarm required when | Suppression required when |
|---|---|---|---|
| 1 | Detached house with service business (< 30% of floor area) | ≥ 7 storeys | fire height ≥ 30 m |
| 2 | Detached house with production or flammable goods trade (< 30%) | ≥ 3 storeys or ≥ 500 m² floor | fire height ≥ 30 m |
| 3 | Apartment building, collective housing, dormitory | ≥ 5 storeys or ≥ 700 m² floor | fire height ≥ 30 m |
| 4 | Nursery, kindergarten, preschool | ≥ 300 m² floor or ≥ 100 children | ≥ 4 storeys and ≥ 5,000 m² floor |
| 5 | School, other education, social care facility | ≥ 5 storeys or ≥ 1,500 m² floor | fire height ≥ 25 m |
| 6 | Hospital, maternity, clinic, other health facility | ≥ 3 storeys or ≥ 300 m² floor | ≥ 2,000 m² floor or fire height ≥ 25 m |
| 7 | Nursing home | Any size | ≥ 500 m² floor |
| 8 | Sports hall, training hall | ≥ 500 m² floor or ≥ 200 seats | fire height ≥ 25 m |
| 9 | Theatre, cinema, circus | ≥ 500 m² floor or ≥ 200 seats | fire height ≥ 25 m |
| 10 | Library | ≥ 300 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 11.1 | Museum, exhibition – basement, semi-basement | Any size | ≥ 200 m² floor |
| 11.2.1 | Museum, exhibition – above ground, 1–2 storeys | ≥ 500 m² floor | ≥ 1,000 m² floor |
| 11.2.2 | Museum, exhibition – above ground, 3+ storeys | Any size | ≥ 500 m² floor |
| 12 | Cultural house, conference centre, multi-purpose hall | ≥ 3 storeys or ≥ 500 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 13.1 | Karaoke, nightclub – basement, semi-basement | Any size | Any size |
| 13.2.1 | Karaoke, nightclub – above ground, 1–2 storeys | Any size | ≥ 500 m² floor |
| 13.2.2 | Karaoke, nightclub – above ground, 3+ storeys | Any size | Any size |
| 14 | Religious facility, provincial-level heritage site | ≥ 4 storeys | fire height ≥ 25 m |
| 15.1 | Market, shopping centre, supermarket – basement, semi-basement | Any size | ≥ 200 m² floor |
| 15.2.1 | Market, shopping centre, supermarket – above ground, 1–2 storeys | Any size | ≥ 3,500 m² floor |
| 15.2.2 | Market, shopping centre, supermarket – above ground, 3+ storeys | Any size | Any size |
| 16 | Restaurant, canteen, aquarium, entertainment, performing arts | ≥ 500 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 17.1 | Electronics, general, convenience, flammable goods store – basement | Any size | ≥ 200 m² floor |
| 17.2 | Electronics, general, convenience, flammable goods store – above ground | ≥ 3 storeys or ≥ 300 m² floor | ≥ 3,500 m² floor or fire height ≥ 25 m |
| 17.3 | Trade in flammable liquids (except in non-combustible packs ≤ 20 L) | Any size | Any size |
| 18 | Hotel, guest house, other accommodation | ≥ 3 storeys or ≥ 700 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 19 | Post office, telecom facility | ≥ 3 storeys or ≥ 500 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 20 | Head office, office, research facility | ≥ 5 storeys or ≥ 500 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 21 | Mixed-use building, mixed-use apartment | ≥ 3 storeys or ≥ 500 m² floor | ≥ 5,000 m² floor or fire height ≥ 25 m |
| 22 | Airport, railway terminal, port, bus station, rest stop, dry port | ≥ 500 m² floor | ≥ 10,000 m² floor or fire height ≥ 25 m |
| 23 | Air traffic control tower | Any size | Any size |
| 24 | Inspection workshop, vehicle registration centre | ≥ 500 m² floor | Not required by Table A.1 |
| 25.1 | Enclosed car park – with basement or 2+ storeys | Any size | Any size |
| 25.2.1 | Enclosed 1-storey car park – resistance I–III, structural class S0 | Any size | ≥ 7,000 m² floor |
| 25.2.2 | Enclosed 1-storey car park – I–III, S1 | Any size | ≥ 3,600 m² floor |
| 25.2.3 | Enclosed 1-storey car park – IV–V, S0 | Any size | ≥ 3,600 m² floor |
| 25.2.4 | Enclosed 1-storey car park – IV–V, S1 | Any size | ≥ 2,000 m² floor |
| 25.2.5 | Enclosed 1-storey car park – IV–V, S2, S3 | Any size | ≥ 1,000 m² floor |
| 25.3.1 | Open car park – every point ≤ 12 m from an open side | ≥ 4 storeys or ≥ 4,000 m² floor | Not required by Table A.1 |
| 25.3.2 | Open car park – some point > 12 m from an open side | Any size | ≥ 4 storeys or ≥ 4,000 m² floor |
| 26 | Car repair garage | Not required by Table A.1 | ≥ 4 repair bays/floor |
| 27 | Aircraft hangar | Any size | ≥ 2,800 m² floor |
| 28 | Road tunnel | length ≥ 500 m | Not required by Table A.1 |
| 29 | Grain processing and storage building | ≥ 500 m² floor | ≥ 3,000 m² floor |
| 30 | Category C warehouse with racks higher than 5.5 m | Any size | Any size |
| 31 | Category B, C warehouse with 2+ storeys | Any size | Any size |
Frequently asked questions
What does a 4-storey, 1,000 m² hotel need?
Table A.1 row 18: automatic alarm required (≥ 3 storeys); below 5 storeys and 1,500 m² standalone detectors are allowed; suppression not required (fire height < 25 m and < 5,000 m²). Extinguishers, emergency lighting and exit signs are still required.
Does a 2,000 m² category C factory need design appraisal?
Yes. Under Annex III of Decree 347/2026, category C factories are covered from 15,000 m³ volume or 2,000 m² floor area ⚠ check the original.
Which regulation replaced TCVN 2622 and TCVN 3890 for provisions?
From 30 Dec 2025 provisions follow QCVN 10:2025/BCA. TCVN 3890:2023 remains voluntary and the QCVN prevails where they differ; TCVN 2622:1995 is not used for new designs.
Applicable documents
Documents in force at the update date, applied from 1 July 2026. TCVN standards are mandatory only when a QCVN refers to them; where they differ, the QCVN prevails.
| Code | Title | Effective from | Status |
|---|---|---|---|
| Luật 55/2024/QH15 | Luật Phòng cháy, chữa cháy và cứu nạn, cứu hộ | 01/07/2025 | In force |
| NĐ 105/2025/NĐ-CP | Chi tiết và biện pháp thi hành Luật PCCC và CNCH | 01/07/2025 | In force ⚠ |
| NĐ 347/2026/NĐ-CP | Sửa đổi NĐ 169/2025, 105/2025, 106/2025, 282/2025 | 15/09/2026 | In force |
| QCVN 10:2025/BCA | Trang bị, bố trí phương tiện PCCC và CNCH cho nhà và công trình | 30/12/2025 | In force |
| QCVN 06:2022/BXD + SĐ1:2023 | An toàn cháy cho nhà và công trình | 16/01/2023 | In force ⚠ |
| TCVN 3890:2023 | Phương tiện PCCC trang bị cho nhà và công trình | Voluntary | In force |
| Luật 135/2025/QH15 | Luật Xây dựng 2025 | 01/07/2026 | In force |
| NĐ 217/2026/NĐ-CP | Quy định chi tiết Luật Xây dựng về quản lý hoạt động xây dựng | 01/07/2026 | In force |